| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24) |
| A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior) |
| A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system accepts reboot in session from unauthenticated users, supporting a denial of service condition. |
| A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account. |
| An Uncontrolled Resource Consumption issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The uncontrolled resource consumption vulnerability could allow an attacker to exhaust the memory resources of the machine, causing a denial of service. |
| A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable). |
| A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files. |
| A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0. |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to escape out of remote PowerSCADA Anywhere applications and launch other processes. |
| Schneider Electric StruxureWare Data Center Expert before 7.4.0 uses cleartext RAM storage for passwords, which might allow remote attackers to obtain sensitive information via unspecified vectors. |
| A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials. |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to specify Arbitrary Server Target Nodes in connection requests to the Secure Gateway and Server components. |
| A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks. |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate. |
| A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. |
| An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application. |
| Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. |
| A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised. |
| An Incorrect Default Permissions issue was discovered in Schneider Electric Wonderware InduSoft Web Studio v8.0 Patch 3 and prior versions. Upon installation, Wonderware InduSoft Web Studio creates a new directory and two files, which are placed in the system's path and can be manipulated by non-administrators. This could allow an authenticated user to escalate his or her privileges. |
| A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack. |