Search Results (379 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2019-10955 1 Rockwellautomation 11 Compactlogix 5370 L1, Compactlogix 5370 L1 Firmware, Compactlogix 5370 L2 and 8 more 2026-06-03 6.1 Medium
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine.
CVE-2017-7903 1 Rockwellautomation 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more 2026-06-03 9.8 Critical
A Weak Password Requirements issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected products use a numeric password with a small maximum character size for the password.
CVE-2017-7898 1 Rockwellautomation 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more 2026-06-03 9.8 Critical
An Improper Restriction of Excessive Authentication Attempts issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. There are no penalties for repeatedly entering incorrect passwords.
CVE-2016-5645 1 Rockwellautomation 6 1766-l32awa, 1766-l32awaa, 1766-l32bwa and 3 more 2026-06-03 7.3 High
Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA devices have a hardcoded SNMP community, which makes it easier for remote attackers to load arbitrary firmware updates by leveraging knowledge of this community.
CVE-2023-5909 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Keepserverex, Opc-aggregator and 5 more 2026-02-25 7.5 High
KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.
CVE-2019-25276 1 Rockwellautomation 2 Factorytalk Activation, Studio 2026-02-05 7.8 High
Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions.
CVE-2025-9278 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. After running a Burp Suite active scan, the device loses ICMP connectivity, causing the web application to become inaccessible.
CVE-2025-9279 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limit Storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
CVE-2025-9281 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive step limit storm tests, the device reboots
CVE-2025-9280 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. Fuzzing performed using Defensics causes the device to become unresponsive, requiring a reboot.
CVE-2025-9282 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive limited storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
CVE-2025-9283 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limits Storms tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
CVE-2025-9464 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. This vulnerability is triggered during fuzzing of multiple CIP classes, which causes the CIP port to become unresponsive.
CVE-2025-9465 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
CVE-2025-9466 1 Rockwellautomation 2 Armorstart Lt, Armorstart Lt Firmware 2026-02-02 7.5 High
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP and CIP grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
CVE-2025-11743 1 Rockwellautomation 1 Compactlogix 5370 2026-01-26 N/A
A denial-of-service security issue in the affected product. The security issue occurs when a malformed CIP forward open message is sent. This could result in a major nonrecoverable fault a restart is required to recover.
CVE-2025-14377 1 Rockwellautomation 1 Verve Asset Manager 2026-01-26 N/A
A security issue was discovered within the legacy Ansible playbook component of Verve Asset Manager, caused by plaintext secrets incorrectly stored when a playbook is running. This component has been retired and has been optional since the 1.36 release in 2024.
CVE-2025-14027 1 Rockwellautomation 1 Controllogix 2026-01-26 N/A
Multiple denial-of-service vulnerabilities exist in the affected product. These issues can be triggered through various crafted inputs, including malformed Class 3 messages, memory leak conditions, and other resource exhaustion scenarios. Exploitation may cause the device to become unresponsive and, in some cases, result in a major nonrecoverable fault. Recovery may require a restart.
CVE-2025-14376 1 Rockwellautomation 1 Verve Asset Manager 2026-01-26 N/A
A security issue was discovered within the legacy ADI server component of Verve Asset Manager, caused by plaintext secrets stored in environment variables on the ADI server. This component has been retired and has been optional since the 1.36 release in 2024.
CVE-2024-21917 1 Rockwellautomation 1 Factorytalk Services Platform 2026-01-15 9.8 Critical
A vulnerability exists in Rockwell Automation FactoryTalk® Service Platform that allows a malicious user to obtain the service token and use it for authentication on another FTSP directory. This is due to the lack of digital signing between the FTSP service token and directory.  If exploited, a malicious user could potentially retrieve user information and modify settings without any authentication.